2820EL Earth Tester, ELCB Tester |
ELCB, 2820EL |
|
Operating Principles.
Earth Leakage Tests.
The testers may be used to check the trip point (Test 1) of the ECLB or the trip time (Test 2). Test 1 is normally used on instantaneous ELCB s while Test 2 is normally used on inverse and fixed time-delay ELCBs.
Test Procedure
Test 1 instantaneous ELCBs A ramp current, increasing at approximately 12 mA/s is introduced between L and E and the point at which the ELCB trips is recorded. To save time and reduce energy dissipation, the starting point of the ramp may be selected. Test 2 - Inverse and fixed time delay ELCBs. A constant current is selected and injected between L-E and the tripping time is recorded. |
Model 2820 Earth Leakage Tester, ELCB Tester is easy to use. It indicates tripping Phase Angle, operates in Voltages from 100V to 450V L-E, Checks ELCB Trip Time and Trip Point (Sensitivity) |
|
ELCB Model 2820EL Earth Leakage Tester |
|
T + M ® |



|
Excess Stock to be cleared while stocks last. > Click for More... |
|
Test our Service and Measure with our Instruments. |
|
Datasheet ELCB Tester, Model 2820EL (362KB) |
|
Features.
· Operating voltage 100-450V L-E. · Rated current 999mA, at 317V AC/50Hz · Checks ELCB trip time and trip point (sensitivity). · Auto-Off/Auto-Ranging. · Phase angle selection (0°/ 180°). · Indicates tripping phase angle. · Impact resistant enclosure. · Over temperature shut-down. · Transient protection. · Suitable for heavy industrial use. · Fused. · EN61010-1 IEC 1010-1 CAT III 450V |
|
We would be very pleased to see you at our offices and show room at the address given above. Please use the maps supplied on our Contact Us page, or call us for directions, should you not be using our GPS Co-Ordinates supplied. It will be our pleasure to assist with your unique requirements. We trust that your visit will be an enjoyable one. T+M® For Good Measure. |
|
Please Note: This is not our complete range, so please contact us for further information on any product that you require, which is not seen on our site. You can call us on +27 (011) 683 4365 or email us by clicking here. |
|
Copyright © 2009—2025 Test and Measurement Instruments C.C. | All rights reserved SEW 2028EL Earth Leakage Tester, ELCB |
|
T + M ® |
|
Brand Names |
|
All brands, trade names, trade marks, and logos are the property of their respective owners. |
|
Ph: +27 (011) 683 4365 / 6 E-mail: sales@instrumentsgroup.co.za
Physical Address: 3 Angelica Ave, Glenvista, Johannesburg, 2091 SOUTH AFRICA
Postal Address: As Above. |
|
This Month’s Special |
|
Click Ex-Series for Spec. Also: Thermal Imagers |